| UPS Rating [Unity Power Factor, kVA=kW, pf.: 1] | | | | | | | | | | | | Efficiency Levels | | | | | | | | | | |
| Rated Power [kVA] | | | | Available in 25 kVA – 1800 kVA | | | AC~AC Mode, On-line | | | | Up To 97% at 100% Rated Load, 95.5% at 50% Rated Load | | | | | | |
| Power Cabinets [kVA] | | | | 150 | 250 | 500 | 180 | 300 | 600 | | | Eco Mode | | | | > 99% | | | | | | |
| Power Modules [kVA] | | | | 25 kVA/ 25 kW; P.f. 1 & 30 kVA/ 30 kW; P.f. 1 | | | Battery Mode | | | | > 96% | | | | | | |
| | | | | | | | | | | | | | | | | | | | | | | |
| System Controller & User Interface | | | | | | | | | | | | Input Characteristics | | | | | | | | | | |
| Display Type | | | | 10.4” Touch Colour LCD, LED System Status Indicators & Keyboard | | | | | | | | Rated Voltage & Range | | 380/ 400/ 415 VAC 3P+N+G -24%~20% 304~478Vac full load; 228V~304Vac, within these tolerances, | | | | | | |
| Fail-Safe Design | | In the event of a power module failure, the system will continue to operate uninterrupted. | | | | the output load shall decrease l nearly as per the minimum utility voltage. | | | | | | |
| | Each power module has its own redundant controlled and static bypass, | | | Rated Frequency & Range | | | | 50/ 60 Hz, 40 ~ 70 Hz | | | | | | |
| | Zero interruption to the load. | | | Power Factor | | | | ≥ 0,99 Active Power Factor Correction Circuitry | | | | | | |
| Available Languages | | | | 5 Standard – EN-TR-SP-FR-RU | | | | | | | | Current Distortion [THDi] | | | | < 3% @ Full Linear Load | | | | | | |
| Power Analyser | | | | kVA, kW, PF Info | | | | | | | | Power Walk-In | | | | Between 1-30 seconds, with 1 s intervals | | | | | | |
| Real Time Clock | | | | Standard with Dynamic Estimation of Back Up Period | | | | | | | | | | | | | | | | | | |
| Event Log | | | | 500 Events with Details & Info, Downloadable via USB-Ethernet | | | | | | | | Battery | Back Up Power | | | | | | | | | | |
| Smart Event Notification
& Scheduled Shutdown for Servers | | Controlled Shutdown. Alerts sent directly to email in the event of a malfunction (Standard | | | Rated Voltage [DC] | | | | ±240VDC, 32 to 44 * 12VDC (Adjustable) VRLA AGM Sealed Lead Acid, Ge | | | | | | |
| | up to 10 users) Text message alerts sent directly to the user in the event of a malfunction (Optional) | | | DC Input Range | | | | Final Discharge Voltage can be 1.65Vdc or 1.7Vdc | | | | | | |
| | Scheduled Automatic Shutdown of Servers on Battery Mode (Standard) | | | Ai-BM | | Manual & Scheduled Battery Test, Scheduled Automatic Shutdown of Servers on Battery Mode, | | | | | | |
| On-Screen Parameters | | Load Bar-Graph, 3 Phase Voltages & Currents & Frequencies, Battery Voltage, Status Info for | | | | (Optional) Real Time Dynamic Remaining Back Up Calculation, | | | | | | |
| | Each Power Module, Static Bypass Module Parameters & Status Info, Battery Temperature | | | Modular Hot-Swap Battery | | | | Optional | | | | | | |
| Alarms | | AC Failure, DC Failure, UPS Module(s) Failure, Bypass Mode, Battery Test Failure, Over Temperature, | | | Charging Capacity | | | | 6A for Each 20 kVA Module, 9A for Each 30 kVA Module | | | | | | |
| | Overload Operation, More Than 60 Other Alarms Listed in User Manual, Audible Alarms | | | Operating Temperature | | | | 25ºC, Temperature Compensated 4 Stage Charging | | | | | | |
| | | | | SNMP-Remote Montoring (MS Windows), TCP/IP, Monitoring Over Web Browser, Hot swappable | | | | | | | | | | | | | |
| Connectivity | | | | smart slot card, RJ -45 interface port, USB, RS232, RS485, MODBUS, Optional GPRS/SMS Wireless, | | | Output Characteristics | | | | | | | | | | |
| | | | | Programmable Dry Contacts | | | Rated Voltage & Accuracy | | | | 380/ 400/ 415 VAC 3P+N ± 1% for Static Load, for Dynamic Load (Step Load) : ± 5% | | | | | | |
| Communication with Power Modules | | | | Serial, Isolated | | | | | | | | Rated f. & Accuracy | | 50/ 60 Hz (Selectable), ±1% ( Synchronized to Mains, Adjustable up to ±5%), | | | | | | |
| Dry Contacts | | | | 3 Programmable Dry Contacts for Input, 11 pcs Parameters, 4 Programmable Dry Contacts for | | | | ±0,1% ( Free Running Mode, Selectable) | | | | | | |
| | | | | Output, 15 pcs Parameters, 19 Dry Contacts, EPO Outputs in Total | | | | | | | | WaveForm | | | | Pure Sine Wave – Sinusoidal | | | | | | |
| | | | | | | | | | | | | Voltage Distortion [THDv] | | | | < 1% (Linear Load), < 4% (Non-Linear Load) according to IEC/EN62040-3 | | | | | | |
| General Characteristics | | | | | | | | | | | | Crest Factor | | | | 3:1 | | | | | | |
| MTBF/ MTTR | | | | Over 600000 Hours | | | | | | | | Unbalanced Load & Acceptable Load PF | | | | Compatible with Operation on 100% Unbalanced Load 0.3 to 1 | | | | | | |
| UPS Type & Technology | | VFI-SS-111 | Online Double Conversion, Three Level Technology | | | Overload Operation | | 60 minutes @ 110% Rated Load, 10 minutes @ 125% Rated Load 1 minutes @ 150% Rated Load | | | | | | |
| | DSP Microprocessor Controlled, Hot-Swap Modular Architecture | | | | Switches to Bypass over 150% Rated Load | | | | | | |
| Isolation Transformer | | | | STANDARD For Flex-T Series | | | | | | | | | | | | | |
| 62040-3 | | | | COMPATIBLE | | | Ambient Characteristics | | | | | | | | | | |
| Power Factor | | | | 0,9 or 1 kVA=kW Unity Power Factor | | | Ambient Temperature | | OPERATING TEMPERATURE RANGE -10ºC – 40ºC | | | | | | |
| True Redundancy | | | | N+X, N+1 Redundancy, True Modular UPS Topology | | | | RECOMMENDED OPERATING TEMPERATURE 15ºC – 25ºC | | | | | | |
| Parallel Configuration [N+1] | | | | Up to 3 Power Cabinets and 1800 Kw | | | | STORAGE TEMPERATURE -30ºC ~ 70ºC | | | | | | |
| | | | | Input Power Limiting, Phase Reversal, Power Module Over Temperature, Over Current, | | | Altitute/ Relative Humidity | | < 1000m above sea level without derating of output power, | | | | | | |
| Standard Protection Features | | | | High Temperature Alert, Smart Short Circuit, Regenerative Load, Current Limiting, Charging Current | | | | output power is derated 1% per 100m from 1000 to 2000m | | | | | | |
| | | | | Limiting, Temperature Compensated Charging, Emergency Power Off (EPO). | | | Noise | | | | < 65dB @ 100% load, 62dB @ 45% load | | | | | | |
| Operating Conditions | | | | 20 ºC, <2400m Above Sea Level, <45% to 55% RH for Best Performance | | | | | | | | | | | | | |
| Cooling/ Isolation | | | | Forced Air Cooling via Redundant Fans – Smart Fan Speed | | | Standards & Certifications | | | | | | | | | | |
| Ma ntenance Bypass | | | | STANDARD | | | Safety | | | | EN 62040-1, EN60950, CE Mark | | | | | | |
| Material [Casing]/ Colour | | | | RAL 7021, BLACK | | | EMC | | | | EN 62040-2 Class C2, CE Mark – Electro-magnetic Compability | | | | | | |
| Cable Entry | | | | REAR/ FRONT BOTTOM | | | Performance | | | | EN 62040-3 (VFI-SS111), CE Mark | | | | | | |
| Operation Modes | | Normal Mode: The input rectifier & output inverter operates in an on-line status to continuously supply power to the critical load. | | | Quality Management | | | | ISO 9001:2015, TUV, CE Mark | | | | | | |
| | Battery Mode: Upon failure of the AC input source, the critical load is being continued to be supplied by the inverter, which derives its power from the battery system without any interruption. | | | | | | | | | | | | | |
| | Recharge: Upon restoration of the AC input source, the UPS simultaneously recharges the battery and provides regulated power to the critical load. | | | Optional Features & Accessories | | | | | | | | | | |
| | Static Bypass: The static bypass shall be used to provide transfer of critical load from the Inverter output to the bypass source. | | | Parallel Redundancy | | | | Horizantal Power Scaling, Optional | | | | | | |
| | Internal Manual/ Mechanical Bypass: The UPS is equipped with an internal, make before break, bypass switch. | | | Hot-Swappable Battery | | | | Optional | | | | | | |
| | | | | | | | | | | | | Extended Runtime | | | | Optional | | | | | | |
| | | | | | | | | | | | | M. Bypass Cab net | | | | Optional | | | | | | |
| | | | | | | | | | | | | Custom Input Voltage | | | | Optional | | | | | | |
| | | | | | | | | | | | | IP Classified Enclosure | | | | Standard IP21, Optional up to IP 66 | | | | | | |
| | | | | | | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | | | | | | |