Three Level, IGBT Rectifier & Inverter UPS | NetXtend HE UPS

NetXtend HE ONLINE UPS
Efficient, Proven, Robust Performance

The NetXtend HE Series UPS is an uninterruptible power supply system for three phase loads & systems. It has also 3Phase Input, Single Phase Output and North American 208V L-L versions available in standard production.

It is a three level topology ups, online, double conversion, high frequency. Best in Class efficiency levels are presented starting with 25% output rated load levels. 

Datacenters, IT companies, large server systems, healthcare facilities and CT, MRI applications, facility loads in buildings, government facilities, private sector headquarters and when correctly sized, there is no issue with the industrial loads & systems.

The design is high frequency, IGBT rectifier and inverter, that means :

Switching losses are minimized, efficiency rates are best-in-class,

Its input power factor correction design makes the input power factor ≥ 0.99, close to 1, like full resistive effect,

Total input current harmonics distortion becomes less than 5%,

Output power factor is 1, kVA=kW, Unity Power Factor and total voltage harmonics distortion is less than 3%,

As a result; The NetXtend HE UPS presents optimized power protection & performance, highest availability & versatility for harshest industrial environments, healthcare and datacenter applications whilst reducing TCO & minimizing the time for ROI.

Three level highly-efficient design dramatically reduces CAPEX & OPEX and gives the power of control to the user while offering minimized RoI period.

NetXtend HE, with TSINE expertise behind and premium components inside, is engineered to meet the needs of demanding environments & businesses worldwide.

 

Pro-IT Isolation Transformers, up to 600V, 5 VA to 4000 kVA

Best Suited for

Facilities, Mixed Loads Use

Industrial Loads & Systems

Medium & Large Sized Enterprises

Healthcare Facilities, Diagnostics and Medical Imaging Systems, CTs, MRIs, Angiography Devices

Financial Institutions, Banks, Banks Headquarters

Buildings of Government, Institutions & Organizations

Airports, Military & Police Stations

Tunnels, Automation & Ventilation Systems

Description

High AC~AC efficiency levels up to 94.5%  

High battery conversion, inverter efficiency as 96.5%

Zero Effect on Utility with Active Power Factor Correction at Input, pf is ≥ 0.99

Low total harmonic distortion for input current as ≤ 4%

Compatible with the toughest application requirements with its super efficient IGBT Rectifier without sacraficing reliability.

Fault tolerant design allows the UPS both protect the connected load and itself from mechanical & electrical forces.

Robust, easy to operate UPS has excellent overload and short circuit capability, superior dynamic response and is easy to maintain.

Compact, easy and ready to install dimensions, minimized footprint, ease to move & locate inside buildings,

160 kVA footprint is only 0,87 m2 (Module IGBT rectifier and inverter), Maximum single unit capacity is 800 kVA in 1,74 m2

Up to 40 kVA, Inbuilt batteries saves from space.

The UPS ProXtend HE is designed for maximized availability and uptime.

Minimized Service and Repair Times, Maximum Time to Repair, MTTR;  Maximized Mean Time Between Failures, MTBF, times

Since a datacenter’ s availability is scaled as 99.99%, Our UPS Systems offers the similar.

Thanks to Lower THDi and Active PFC at Input Side, Cost savings on Low Voltage Installation in UpStream The UPS

Reduced installation and operation costs, minimized footprint, minimized UPS/Electrical Room Requirements.

Operational expenditure is optimized with a complete and cost effective life cycle.

The high efficiency of the complete UPS (AC/AC), as well as of the inverter part (DC/AC), even at partial load, helps optimizing both HVAC system and battery sizing.

Less maintenance needs, advanced battery management which leads extended battery lifetime and extended lifetimes for lifed items means long replacement times and avoiding repeating costs.

 

The Result: Reduced Total Cost of Ownership & Fast Return of Investment

Thanks to Max. Availability and Max. Uptime for The Businesses, Minimized Downtimes.



Features

Easy & Fast Serviceability, Fast Dynamic Solutions to On-Site Problems

Robust, Reliable Operation, Proven Track Record and Use

Compact, highly-efficient, cutting-edge technology with built-in features to adapt to diverse environments and requirements.

IGBT Rectifier/ IGBT Inverter, Double Conversion Architecture, Available with Various Global Voltages

Seamless transfer between sources, high generator compability

High efficiency rates as up to 94%, even at partial load

Small footprint, high power density

Fault-tolerant, over-engineered design, DSP ultra high speed control architecture

High output short-circuit clearance capability

High output short-circuit clearance capability

Prolonged battery lifetime, budget -friendly lifetime.

Reliable Redundant parallel operation

High communication and connectivity capabilities

Options for Enclosure IP Classifications, Isolation Transformers,

Additional information

Voltage Class

600V

Input Voltage

, , , , ,

Output Voltage

, , , ,

Ratings

50W – 500 kVA

Voltage & Frequency

208-220-380- 400-440-480- 600Vac Others on Request

Windings Material

Copper or Aluminum

Efficiency

97% or higher

Form Factor

, ,

Transformer Design

Delta/Star, without neutral at the input

Neutral Line Capacity

100% of nominal

Dielectric Strength

4,2kVac min

CMNA

146 dB (with triple shielding)

Overload Capacity

200% for 30 sec, 500% for 1 sec,
1000% for 1 cycle

Load Regulation

±1% at full load.

Audible noise

< 45 dB at 1mt.

Enclosure type

IP21, metal, epoxy painted RAL7035

Operating temperature

0°C to 50°C ambient

Operating humidity

up to 90% relative (non condensing)

Operating altitude

up to 1000mt above sea level