Oil & Gas Industry, Highly Customizable UPS AC & DC UPS Systems
Cathodic Protection Rectifier Systems
Rectifiers and Inverters
IEC 60529
IEC 62040-1, 2, 3
UL, CSA
UPS or Genset Capacity & Performance Testing
Datacenter Simulation
Marine or Military Applications Load Testing
TSINE Load Ultima Series Precise, Over-Engineered Systems and Solutions
IP Rated or Containerized Designs
RLC or DC Load Banks
TSINE LT9000 Series Three Phase UPS | Aa cutting-edge, highly efficient uninterruptible power supply
Dyna-Ion Series Lithium Battery Solution by tsinepower.
Standard 6000 cycles lifetime and 10000 cycles extended cell lifetime.
Containerized Power Systems
Marine, Telecom, Railways, Industrial & BESS - Micro-grid or Utility Operator Industries
Best-in-Class, Plug & Play Ready to Go Designs.
Mobile
Containerized
Centralized
Isolated
Pro-IT Series Isolation Transformers
TSINE Pro-IT Series isolation transformers are mainly for isolating the input power available in its primary windings from the output power in its secondary windings, thus leads a reliable supply for systems & loads connected to the secondary windings. Besides the isolation, Pro-IT Series helps to create a fresh neutral point and/or helps to increase/ decrease the voltage from the primary to secondary windings.
Pro-IT is for max. reliability and total isolation of the systems from power source disturbances/ fluctuations.
Industrial interconnection converter architecture, the new generation of Static Frequency Converter (SFC) allows the connection of 60 Hz powered equipment to a 50 Hz supply network and 50 Hz powered equipment to a 60 Hz supply network.
Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.
UPS Rating [Unity Power Factor, kVA=kW, pf.: 1] | Efficiency Levels | ||||||||||||||||||||||
Rated Power [kVA] | Available in 25 kVA – 1800 kVA | AC~AC Mode, On-line | Up To 97% at 100% Rated Load, 95.5% at 50% Rated Load | ||||||||||||||||||||
Power Cabinets [kVA] | 150 | 250 | 500 | 180 | 300 | 600 | Eco Mode | > 99% | |||||||||||||||
Power Modules [kVA] | 25 kVA/ 25 kW; P.f. 1 & 30 kVA/ 30 kW; P.f. 1 | Battery Mode | > 96% | ||||||||||||||||||||
System Controller & User Interface | Input Characteristics | ||||||||||||||||||||||
Display Type | 10.4” Touch Colour LCD, LED System Status Indicators & Keyboard | Rated Voltage & Range | 380/ 400/ 415 VAC 3P+N+G -24%~20% 304~478Vac full load; 228V~304Vac, within these tolerances, | ||||||||||||||||||||
Fail-Safe Design | In the event of a power module failure, the system will continue to operate uninterrupted. | the output load shall decrease l nearly as per the minimum utility voltage. | |||||||||||||||||||||
Each power module has its own redundant controlled and static bypass, | Rated Frequency & Range | 50/ 60 Hz, 40 ~ 70 Hz | |||||||||||||||||||||
Zero interruption to the load. | Power Factor | ≥ 0,99 Active Power Factor Correction Circuitry | |||||||||||||||||||||
Available Languages | 5 Standard – EN-TR-SP-FR-RU | Current Distortion [THDi] | < 3% @ Full Linear Load | ||||||||||||||||||||
Power Analyser | kVA, kW, PF Info | Power Walk-In | Between 1-30 seconds, with 1 s intervals | ||||||||||||||||||||
Real Time Clock | Standard with Dynamic Estimation of Back Up Period | ||||||||||||||||||||||
Event Log | 500 Events with Details & Info, Downloadable via USB-Ethernet | Battery | Back Up Power | |||||||||||||||||||||
Smart Event Notification & Scheduled Shutdown for Servers | Controlled Shutdown. Alerts sent directly to email in the event of a malfunction (Standard | Rated Voltage [DC] | ±240VDC, 32 to 44 * 12VDC (Adjustable) VRLA AGM Sealed Lead Acid, Ge | ||||||||||||||||||||
up to 10 users) Text message alerts sent directly to the user in the event of a malfunction (Optional) | DC Input Range | Final Discharge Voltage can be 1.65Vdc or 1.7Vdc | |||||||||||||||||||||
Scheduled Automatic Shutdown of Servers on Battery Mode (Standard) | Ai-BM | Manual & Scheduled Battery Test, Scheduled Automatic Shutdown of Servers on Battery Mode, | |||||||||||||||||||||
On-Screen Parameters | Load Bar-Graph, 3 Phase Voltages & Currents & Frequencies, Battery Voltage, Status Info for | (Optional) Real Time Dynamic Remaining Back Up Calculation, | |||||||||||||||||||||
Each Power Module, Static Bypass Module Parameters & Status Info, Battery Temperature | Modular Hot-Swap Battery | Optional | |||||||||||||||||||||
Alarms | AC Failure, DC Failure, UPS Module(s) Failure, Bypass Mode, Battery Test Failure, Over Temperature, | Charging Capacity | 6A for Each 20 kVA Module, 9A for Each 30 kVA Module | ||||||||||||||||||||
Overload Operation, More Than 60 Other Alarms Listed in User Manual, Audible Alarms | Operating Temperature | 25ºC, Temperature Compensated 4 Stage Charging | |||||||||||||||||||||
SNMP-Remote Montoring (MS Windows), TCP/IP, Monitoring Over Web Browser, Hot swappable | |||||||||||||||||||||||
Connectivity | smart slot card, RJ -45 interface port, USB, RS232, RS485, MODBUS, Optional GPRS/SMS Wireless, | Output Characteristics | |||||||||||||||||||||
Programmable Dry Contacts | Rated Voltage & Accuracy | 380/ 400/ 415 VAC 3P+N ± 1% for Static Load, for Dynamic Load (Step Load) : ± 5% | |||||||||||||||||||||
Communication with Power Modules | Serial, Isolated | Rated f. & Accuracy | 50/ 60 Hz (Selectable), ±1% ( Synchronized to Mains, Adjustable up to ±5%), | ||||||||||||||||||||
Dry Contacts | 3 Programmable Dry Contacts for Input, 11 pcs Parameters, 4 Programmable Dry Contacts for | ±0,1% ( Free Running Mode, Selectable) | |||||||||||||||||||||
Output, 15 pcs Parameters, 19 Dry Contacts, EPO Outputs in Total | WaveForm | Pure Sine Wave – Sinusoidal | |||||||||||||||||||||
Voltage Distortion [THDv] | < 1% (Linear Load), < 4% (Non-Linear Load) according to IEC/EN62040-3 | ||||||||||||||||||||||
General Characteristics | Crest Factor | 3:1 | |||||||||||||||||||||
MTBF/ MTTR | Over 600000 Hours | Unbalanced Load & Acceptable Load PF | Compatible with Operation on 100% Unbalanced Load 0.3 to 1 | ||||||||||||||||||||
UPS Type & Technology | VFI-SS-111 | Online Double Conversion, Three Level Technology | Overload Operation | 60 minutes @ 110% Rated Load, 10 minutes @ 125% Rated Load 1 minutes @ 150% Rated Load | ||||||||||||||||||||
DSP Microprocessor Controlled, Hot-Swap Modular Architecture | Switches to Bypass over 150% Rated Load | ||||||||||||||||||||||
Isolation Transformer | STANDARD For Flex-T Series | ||||||||||||||||||||||
62040-3 | COMPATIBLE | Ambient Characteristics | |||||||||||||||||||||
Power Factor | 0,9 or 1 kVA=kW Unity Power Factor | Ambient Temperature | OPERATING TEMPERATURE RANGE -10ºC – 40ºC | ||||||||||||||||||||
True Redundancy | N+X, N+1 Redundancy, True Modular UPS Topology | RECOMMENDED OPERATING TEMPERATURE 15ºC – 25ºC | |||||||||||||||||||||
Parallel Configuration [N+1] | Up to 3 Power Cabinets and 1800 Kw | STORAGE TEMPERATURE -30ºC ~ 70ºC | |||||||||||||||||||||
Input Power Limiting, Phase Reversal, Power Module Over Temperature, Over Current, | Altitute/ Relative Humidity | < 1000m above sea level without derating of output power, | |||||||||||||||||||||
Standard Protection Features | High Temperature Alert, Smart Short Circuit, Regenerative Load, Current Limiting, Charging Current | output power is derated 1% per 100m from 1000 to 2000m | |||||||||||||||||||||
Limiting, Temperature Compensated Charging, Emergency Power Off (EPO). | Noise | < 65dB @ 100% load, 62dB @ 45% load | |||||||||||||||||||||
Operating Conditions | 20 ºC, <2400m Above Sea Level, <45% to 55% RH for Best Performance | ||||||||||||||||||||||
Cooling/ Isolation | Forced Air Cooling via Redundant Fans – Smart Fan Speed | Standards & Certifications | |||||||||||||||||||||
Ma ntenance Bypass | STANDARD | Safety | EN 62040-1, EN60950, CE Mark | ||||||||||||||||||||
Material [Casing]/ Colour | RAL 7021, BLACK | EMC | EN 62040-2 Class C2, CE Mark – Electro-magnetic Compability | ||||||||||||||||||||
Cable Entry | REAR/ FRONT BOTTOM | Performance | EN 62040-3 (VFI-SS111), CE Mark | ||||||||||||||||||||
Operation Modes | Normal Mode: The input rectifier & output inverter operates in an on-line status to continuously supply power to the critical load. | Quality Management | ISO 9001:2015, TUV, CE Mark | ||||||||||||||||||||
Battery Mode: Upon failure of the AC input source, the critical load is being continued to be supplied by the inverter, which derives its power from the battery system without any interruption. | |||||||||||||||||||||||
Recharge: Upon restoration of the AC input source, the UPS simultaneously recharges the battery and provides regulated power to the critical load. | Optional Features & Accessories | ||||||||||||||||||||||
Static Bypass: The static bypass shall be used to provide transfer of critical load from the Inverter output to the bypass source. | Parallel Redundancy | Horizantal Power Scaling, Optional | |||||||||||||||||||||
Internal Manual/ Mechanical Bypass: The UPS is equipped with an internal, make before break, bypass switch. | Hot-Swappable Battery | Optional | |||||||||||||||||||||
Extended Runtime | Optional | ||||||||||||||||||||||
M. Bypass Cab net | Optional | ||||||||||||||||||||||
Custom Input Voltage | Optional | ||||||||||||||||||||||
IP Classified Enclosure | Standard IP21, Optional up to IP 66 | ||||||||||||||||||||||
Tab Content
Totally isolates distribution system from hazards of harmonics, power disturbances & voltage fluctuations.
Delta/ Star design does not require any neutral availability at the input side, thus creates a fresh ground-neutral reference for output & connected loads, systems.
Reduces sudden current fluctuations.
Proven, reliable galvanic isolation.
Conventional 208-220-380- 400-440-480- 600Vac as standard, others on request.
Ultra protection against input supply fluctuations & distortions.
Equal-sized neutral conductor, neutral bus size configured to accommodate at least 100% of the rated current as well as the phase conductors.
Continuous output power for the environment temperatures up to 50°C
High quality pure electrolytic copper windings (Optional aluminium), high magnetic permeability iron core.
Air spaced welding which minimizes body earthing resistance
Advanced engineering, enhanced magnetic and resistive properties.
Meets DOE 2016 and NEMA TP-1 efficiency requirements, efficient is 97% and above.
Vacuum varnishing finish thus leads increasing efficiency by reducing heat losses, protection against humidity & wet environments, reduced operating audible noise
Voltage transformation within a wide range of input & output voltage like 208 to 400Vac or 380 to 415Vac.
Completely accessible for service and maintenance from front panel.
Top and bottom cable entry
Meets standards EN 61558-2-2, EN61558-2-4, CEI 96-8, VDE 0550, BS 171
Transformers include a versatile bonding/grounding bar affixed to the bottom panel as standard, to provide compliance with NEC 450.10(A)
In-built or external transformer cabinets
Integrated distribution cabinets
Integrated accessory cabinet
Voltage Class | 600V |
---|---|
Input Voltage | 100/ 110/ 115/ 120/ 127VAC Single Phase, 200/ 208/ 220/ 230/ 240/ 277VAC Single Phase, 190/ 200/ 208/ 220 3P+N, 110/ 115/ 120/ 127 1P+N, 208/ 220/ 230/ 240 3P+N, 360/ 380/ 400/ 415/ 440Vac 3P+N |
Output Voltage | 100/ 110/ 115/ 120/ 127VAC Single Phase, 190/ 200/ 208/ 220VAC Three Phase, 200/ 208/ 220/ 230/ 240/ 277VAC Single Phase, 380/ 400/ 415VAC Three Phase, 440/ 480VAC Three Phase |
Ratings | 50W – 500 kVA |
Voltage & Frequency | 208-220-380- 400-440-480- 600Vac Others on Request |
Windings Material | Copper or Aluminum |
Efficiency | 97% or higher |
Form Factor | |
Transformer Design | Delta/Star, without neutral at the input |
Neutral Line Capacity | 100% of nominal |
Dielectric Strength | 4,2kVac min |
CMNA | 146 dB (with triple shielding) |
Overload Capacity | 200% for 30 sec, 500% for 1 sec, |
Load Regulation | ±1% at full load. |
Audible noise | < 45 dB at 1mt. |
Enclosure type | IP21, metal, epoxy painted RAL7035 |
Operating temperature | 0°C to 50°C ambient |
Operating humidity | up to 90% relative (non condensing) |
Operating altitude | up to 1000mt above sea level |