Oil & Gas Industry, Highly Customizable UPS AC & DC UPS Systems
Cathodic Protection Rectifier Systems
Rectifiers and Inverters
IEC 60529
IEC 62040-1, 2, 3
UL, CSA
UPS or Genset Capacity & Performance Testing
Datacenter Simulation
Marine or Military Applications Load Testing
TSINE Load Ultima Series Precise, Over-Engineered Systems and Solutions
IP Rated or Containerized Designs
RLC or DC Load Banks
TSINE LT9000 Series Three Phase UPS | Aa cutting-edge, highly efficient uninterruptible power supply
Dyna-Ion Series Lithium Battery Solution by tsinepower.
Standard 6000 cycles lifetime and 10000 cycles extended cell lifetime.
Containerized Power Systems
Marine, Telecom, Railways, Industrial & BESS - Micro-grid or Utility Operator Industries
Best-in-Class, Plug & Play Ready to Go Designs.
Mobile
Containerized
Centralized
Isolated
A UPS with Proven Reliability & Robustness for Diverse Requirements
The UPS ProXtend HE is engineered to supply secure, clean & continuous power to the critical loads & systems with diverse requirements.
The UPS has high levels of efficiency, cost effective operation, lower total cost of ownership via less maintenance needs, advanced battery management which leads extended battery lifetime and extended lifetimes for lifed items.
It ensures the permanent availability for production facilities, sensitive electronics in medical imaging and diagnosis, facilities, banks and financial instutitions, datacenters-IT environment-big data and vast range of applications and systems globally.
The ProXtend HE has a very long track record in system availability and use in 5 continents and over 70 countries including USA, Canada and Australia.
Best Suited for
Facilities, Mixed Loads Use
Industrial Loads & Systems
Medium & Large Sized Enterprises
Healthcare Facilities, Diagnostics and Medical Imaging Systems, CTs, MRIs, Angiography Devices
Financial Institutions, Banks, Banks Headquarters
Buildings of Government, Institutions & Organizations
Industrial interconnection converter architecture, the new generation of Static Frequency Converter (SFC) allows the connection of 60 Hz powered equipment to a 50 Hz supply network and 50 Hz powered equipment to a 60 Hz supply network.
Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.
UPS Rating [Unity Power Factor, kVA=kW, pf.: 1] | Efficiency Levels | ||||||||||||||||||||||
Rated Power [kVA] | Available in 25 kVA – 1800 kVA | AC~AC Mode, On-line | Up To 97% at 100% Rated Load, 95.5% at 50% Rated Load | ||||||||||||||||||||
Power Cabinets [kVA] | 150 | 250 | 500 | 180 | 300 | 600 | Eco Mode | > 99% | |||||||||||||||
Power Modules [kVA] | 25 kVA/ 25 kW; P.f. 1 & 30 kVA/ 30 kW; P.f. 1 | Battery Mode | > 96% | ||||||||||||||||||||
System Controller & User Interface | Input Characteristics | ||||||||||||||||||||||
Display Type | 10.4” Touch Colour LCD, LED System Status Indicators & Keyboard | Rated Voltage & Range | 380/ 400/ 415 VAC 3P+N+G -24%~20% 304~478Vac full load; 228V~304Vac, within these tolerances, | ||||||||||||||||||||
Fail-Safe Design | In the event of a power module failure, the system will continue to operate uninterrupted. | the output load shall decrease l nearly as per the minimum utility voltage. | |||||||||||||||||||||
Each power module has its own redundant controlled and static bypass, | Rated Frequency & Range | 50/ 60 Hz, 40 ~ 70 Hz | |||||||||||||||||||||
Zero interruption to the load. | Power Factor | ≥ 0,99 Active Power Factor Correction Circuitry | |||||||||||||||||||||
Available Languages | 5 Standard – EN-TR-SP-FR-RU | Current Distortion [THDi] | < 3% @ Full Linear Load | ||||||||||||||||||||
Power Analyser | kVA, kW, PF Info | Power Walk-In | Between 1-30 seconds, with 1 s intervals | ||||||||||||||||||||
Real Time Clock | Standard with Dynamic Estimation of Back Up Period | ||||||||||||||||||||||
Event Log | 500 Events with Details & Info, Downloadable via USB-Ethernet | Battery | Back Up Power | |||||||||||||||||||||
Smart Event Notification & Scheduled Shutdown for Servers | Controlled Shutdown. Alerts sent directly to email in the event of a malfunction (Standard | Rated Voltage [DC] | ±240VDC, 32 to 44 * 12VDC (Adjustable) VRLA AGM Sealed Lead Acid, Ge | ||||||||||||||||||||
up to 10 users) Text message alerts sent directly to the user in the event of a malfunction (Optional) | DC Input Range | Final Discharge Voltage can be 1.65Vdc or 1.7Vdc | |||||||||||||||||||||
Scheduled Automatic Shutdown of Servers on Battery Mode (Standard) | Ai-BM | Manual & Scheduled Battery Test, Scheduled Automatic Shutdown of Servers on Battery Mode, | |||||||||||||||||||||
On-Screen Parameters | Load Bar-Graph, 3 Phase Voltages & Currents & Frequencies, Battery Voltage, Status Info for | (Optional) Real Time Dynamic Remaining Back Up Calculation, | |||||||||||||||||||||
Each Power Module, Static Bypass Module Parameters & Status Info, Battery Temperature | Modular Hot-Swap Battery | Optional | |||||||||||||||||||||
Alarms | AC Failure, DC Failure, UPS Module(s) Failure, Bypass Mode, Battery Test Failure, Over Temperature, | Charging Capacity | 6A for Each 20 kVA Module, 9A for Each 30 kVA Module | ||||||||||||||||||||
Overload Operation, More Than 60 Other Alarms Listed in User Manual, Audible Alarms | Operating Temperature | 25ºC, Temperature Compensated 4 Stage Charging | |||||||||||||||||||||
SNMP-Remote Montoring (MS Windows), TCP/IP, Monitoring Over Web Browser, Hot swappable | |||||||||||||||||||||||
Connectivity | smart slot card, RJ -45 interface port, USB, RS232, RS485, MODBUS, Optional GPRS/SMS Wireless, | Output Characteristics | |||||||||||||||||||||
Programmable Dry Contacts | Rated Voltage & Accuracy | 380/ 400/ 415 VAC 3P+N ± 1% for Static Load, for Dynamic Load (Step Load) : ± 5% | |||||||||||||||||||||
Communication with Power Modules | Serial, Isolated | Rated f. & Accuracy | 50/ 60 Hz (Selectable), ±1% ( Synchronized to Mains, Adjustable up to ±5%), | ||||||||||||||||||||
Dry Contacts | 3 Programmable Dry Contacts for Input, 11 pcs Parameters, 4 Programmable Dry Contacts for | ±0,1% ( Free Running Mode, Selectable) | |||||||||||||||||||||
Output, 15 pcs Parameters, 19 Dry Contacts, EPO Outputs in Total | WaveForm | Pure Sine Wave – Sinusoidal | |||||||||||||||||||||
Voltage Distortion [THDv] | < 1% (Linear Load), < 4% (Non-Linear Load) according to IEC/EN62040-3 | ||||||||||||||||||||||
General Characteristics | Crest Factor | 3:1 | |||||||||||||||||||||
MTBF/ MTTR | Over 600000 Hours | Unbalanced Load & Acceptable Load PF | Compatible with Operation on 100% Unbalanced Load 0.3 to 1 | ||||||||||||||||||||
UPS Type & Technology | VFI-SS-111 | Online Double Conversion, Three Level Technology | Overload Operation | 60 minutes @ 110% Rated Load, 10 minutes @ 125% Rated Load 1 minutes @ 150% Rated Load | ||||||||||||||||||||
DSP Microprocessor Controlled, Hot-Swap Modular Architecture | Switches to Bypass over 150% Rated Load | ||||||||||||||||||||||
Isolation Transformer | STANDARD For Flex-T Series | ||||||||||||||||||||||
62040-3 | COMPATIBLE | Ambient Characteristics | |||||||||||||||||||||
Power Factor | 0,9 or 1 kVA=kW Unity Power Factor | Ambient Temperature | OPERATING TEMPERATURE RANGE -10ºC – 40ºC | ||||||||||||||||||||
True Redundancy | N+X, N+1 Redundancy, True Modular UPS Topology | RECOMMENDED OPERATING TEMPERATURE 15ºC – 25ºC | |||||||||||||||||||||
Parallel Configuration [N+1] | Up to 3 Power Cabinets and 1800 Kw | STORAGE TEMPERATURE -30ºC ~ 70ºC | |||||||||||||||||||||
Input Power Limiting, Phase Reversal, Power Module Over Temperature, Over Current, | Altitute/ Relative Humidity | < 1000m above sea level without derating of output power, | |||||||||||||||||||||
Standard Protection Features | High Temperature Alert, Smart Short Circuit, Regenerative Load, Current Limiting, Charging Current | output power is derated 1% per 100m from 1000 to 2000m | |||||||||||||||||||||
Limiting, Temperature Compensated Charging, Emergency Power Off (EPO). | Noise | < 65dB @ 100% load, 62dB @ 45% load | |||||||||||||||||||||
Operating Conditions | 20 ºC, <2400m Above Sea Level, <45% to 55% RH for Best Performance | ||||||||||||||||||||||
Cooling/ Isolation | Forced Air Cooling via Redundant Fans – Smart Fan Speed | Standards & Certifications | |||||||||||||||||||||
Ma ntenance Bypass | STANDARD | Safety | EN 62040-1, EN60950, CE Mark | ||||||||||||||||||||
Material [Casing]/ Colour | RAL 7021, BLACK | EMC | EN 62040-2 Class C2, CE Mark – Electro-magnetic Compability | ||||||||||||||||||||
Cable Entry | REAR/ FRONT BOTTOM | Performance | EN 62040-3 (VFI-SS111), CE Mark | ||||||||||||||||||||
Operation Modes | Normal Mode: The input rectifier & output inverter operates in an on-line status to continuously supply power to the critical load. | Quality Management | ISO 9001:2015, TUV, CE Mark | ||||||||||||||||||||
Battery Mode: Upon failure of the AC input source, the critical load is being continued to be supplied by the inverter, which derives its power from the battery system without any interruption. | |||||||||||||||||||||||
Recharge: Upon restoration of the AC input source, the UPS simultaneously recharges the battery and provides regulated power to the critical load. | Optional Features & Accessories | ||||||||||||||||||||||
Static Bypass: The static bypass shall be used to provide transfer of critical load from the Inverter output to the bypass source. | Parallel Redundancy | Horizantal Power Scaling, Optional | |||||||||||||||||||||
Internal Manual/ Mechanical Bypass: The UPS is equipped with an internal, make before break, bypass switch. | Hot-Swappable Battery | Optional | |||||||||||||||||||||
Extended Runtime | Optional | ||||||||||||||||||||||
M. Bypass Cab net | Optional | ||||||||||||||||||||||
Custom Input Voltage | Optional | ||||||||||||||||||||||
IP Classified Enclosure | Standard IP21, Optional up to IP 66 | ||||||||||||||||||||||
Tab Content
High AC~AC efficiency levels up to 94.5%
High battery conversion, inverter efficiency as 96.5%
Zero Effect on Utility with Active Power Factor Correction at Input, pf is ≥ 0.99
Low total harmonic distortion for input current as ≤ 4%
Compatible with the toughest application requirements with its super efficient IGBT Rectifier without sacraficing reliability.
Fault tolerant design allows the UPS both protect the connected load and itself from mechanical & electrical forces.
Robust, easy to operate UPS has excellent overload and short circuit capability, superior dynamic response and is easy to maintain.
Compact, easy and ready to install dimensions, minimized footprint, ease to move & locate inside buildings,
160 kVA footprint is only 0,87 m2 (Module IGBT rectifier and inverter), Maximum single unit capacity is 800 kVA in 1,74 m2
Up to 40 kVA, Inbuilt batteries saves from space.
The UPS ProXtend HE is designed for maximized availability and uptime.
Minimized Service and Repair Times, Maximum Time to Repair, MTTR; Maximized Mean Time Between Failures, MTBF, times
Since a datacenter’ s availability is scaled as 99.99%, Our UPS Systems offers the similar.
Thanks to Lower THDi and Active PFC at Input Side, Cost savings on Low Voltage Installation in UpStream The UPS
Reduced installation and operation costs, minimized footprint, minimized UPS/Electrical Room Requirements.
Operational expenditure is optimized with a complete and cost effective life cycle.
The high efficiency of the complete UPS (AC/AC), as well as of the inverter part (DC/AC), even at partial load, helps optimizing both HVAC system and battery sizing.
Less maintenance needs, advanced battery management which leads extended battery lifetime and extended lifetimes for lifed items means long replacement times and avoiding repeating costs.
The Result: Reduced Total Cost of Ownership & Fast Return of Investment
Thanks to Max. Availability and Max. Uptime for The Businesses, Minimized Downtimes.
Easy & Fast Serviceability, Fast Dynamic Solutions to On-Site Problems
Robust, Reliable Operation, Proven Track Record and Use
Compact, highly-efficient, cutting-edge technology with built-in features to adapt to diverse environments and requirements.
IGBT Rectifier/ IGBT Inverter, Double Conversion Architecture, Available with Various Global Voltages
Seamless transfer between sources, high generator compability
High efficiency rates as up to 94%, even at partial load
Small footprint, high power density
Fault-tolerant, over-engineered design, DSP ultra high speed control architecture
High output short-circuit clearance capability
High output short-circuit clearance capability
Prolonged battery lifetime, budget -friendly lifetime.
Reliable Redundant parallel operation
High communication and connectivity capabilities
Options for Enclosure IP Classifications, Isolation Transformers,
Voltage Class | 600V |
---|---|
Input Voltage | 100/ 110/ 115/ 120/ 127VAC Single Phase, 200/ 208/ 220/ 230/ 240/ 277VAC Single Phase, 190/ 200/ 208/ 220 3P+N, 110/ 115/ 120/ 127 1P+N, 208/ 220/ 230/ 240 3P+N, 360/ 380/ 400/ 415/ 440Vac 3P+N |
Output Voltage | 100/ 110/ 115/ 120/ 127VAC Single Phase, 190/ 200/ 208/ 220VAC Three Phase, 200/ 208/ 220/ 230/ 240/ 277VAC Single Phase, 380/ 400/ 415VAC Three Phase, 440/ 480VAC Three Phase |
Ratings | 50W – 500 kVA |
Voltage & Frequency | 208-220-380- 400-440-480- 600Vac Others on Request |
Windings Material | Copper or Aluminum |
Efficiency | 97% or higher |
Form Factor | |
Transformer Design | Delta/Star, without neutral at the input |
Neutral Line Capacity | 100% of nominal |
Dielectric Strength | 4,2kVac min |
CMNA | 146 dB (with triple shielding) |
Overload Capacity | 200% for 30 sec, 500% for 1 sec, |
Load Regulation | ±1% at full load. |
Audible noise | < 45 dB at 1mt. |
Enclosure type | IP21, metal, epoxy painted RAL7035 |
Operating temperature | 0°C to 50°C ambient |
Operating humidity | up to 90% relative (non condensing) |
Operating altitude | up to 1000mt above sea level |